  • Complete Data Acquisition Systems
  • Analog and Digital I/O Models Available
  • RS485 Serial Communications Interface
  • MODBUS® RTU Protocol
  • Up to 25 Conversions per Second
  • 500 Vrms Analog Input or Analog Output Isolation
  • 16-Bit Analog Input Measurement Resolution
  • Continuous Self-Calibration; No Adjustments Required
  • Programmable Analog Input Digital Filters
  • Requires 10V to 30 Vdc Unregulated Supply
  • Transient Suppression on Serial RS485 Data Lines
  • Removable Screw Terminal Plug Connectors Supplied
  • Process Monitoring and Control
  • Remote Data Logging to any Host Computer
  • Product Testing
  • Direct Connection to PLC

  • The D6000 Series modules are a family of completedata acquisition modules for use in process controlsystems. The analog input models can measureprocess signals such as thermocouples, 4 to 20 mAloops, and discrete contact closures. The analogoutput models can generate voltage or current signalsfor controlling annunciators or valves. The digital inputand output models can sense the state of remotedigital signals or control solid state relays. Completedata acquisition systems can be created with easewith the D6000 modules and a host supervisorycomputer or programmable logic controller.The modules provide direct connection to a widevariety of sensors and annunciators. They performall signal conditioning and linearization and containno pots or DIP switches. All user-selectable settings,such as ranges, communications settings are storedin nonvolatile EEPROM, which maintains these valueseven after power is removed.The D6000 series modules communicate with ahost computer using the MODBUS RTU protocol.The MODBUS RTU protocol is widely recognizedthroughout the data acquisition industry by andsupported by almost all commercially availableprocess control programs and supervisory host PLC’s.

    This binary protocol communicates via a two-wireRS485 serial interface. The key to the product conceptis that the modules are easy to connect and use. Youdo not need engineering experience in complicateddata acquisition hardware. With the modules, anyonefamiliar with a personal computer can construct a dataacquisition system.This modular approach to data acquisition is veryflexible, easy to use and cost effective. The modules canbe mixed and matched to fit your application. They canbe placed remote from the host and from each other.The D6000 series is completely hardware compatiblewith the D1000M, D1700M, D3000M and D5000M seriesmodules. Meaning, they can all be mixed and matchedon one RS485 serial communications line. Each moduleis identified by a unique user-programmable address.This addressing technique allows modules to beinterrogated in any order.

    ANALOG INPUT MODULES
    The D6100 through D6400 Series analog input modulescontain seven input channels and make up a completedata acquisition system. Each unit contains analogsignal conditioning circuits optimized for a specific inputtype. The amplified sensor signals are converted todigital data with a microprocessor-controlled integratingA/D converter. Offset and gain errors in the analogcircuitry are continuously monitored and corrected usingmicroprocessor techniques.The analog input modules output the resultant digitaldata as unsigned integer percentage of full-scale valuesthat are compatible with the MODBUS RTU protocol.The modules continuously convert data at the rate ofup to 25 conversions per second and store the latestresult in a buffer. Host processors may request data bysending a MODBUS query to the module. The D6000series modules will instantly respond by communicatingthe memory buffer data back to the host processor. Upto 247 modules may be linked to a single RS485 port.

    ANALOG OUTPUT MODULES
    The D6500 analog output modules contain two 12-bitdigital to analog converters (DAC) for generating eithervoltage or current output signals. The output signaltype for each DAC is user selectable and each DAC isindependently controlled via a host computer using theMODBUS RTU protocol. Two voltage and two currentranges are available.The D6500 analog output modules also containprogrammable features such as output slew rate,a communications watchdog timer, programmablestartup signal value, and an 8-bit analog to digitalconverter for analog readback the output signal. Thecommunications watchdog timer can be used to movethe analog output signal to a known “safe” condition inthe event of a communications failure.

    DIGITAL INPUT MODULES
    The D6710 digital input modules contain 15 individualsignal inputs for monitoring logic levels, contactclosures, or other ON/OFF signals in a data acquisitionsystem. Each discrete input terminal contains a pullupbiasing resistor allowing for direct connection to aset of contacts. The input terminals can accept signalsbetween ±30 Vdc without damage.

    DIGITAL OUTPUT MODULESThe D6720 digital output modules contain 15 individualopen-collector transistor outputs for controllingannunciators, lamps, or other devices that require anON/OFF signal.The D6720 digital output modules also containprogrammable features such as a communicationswatchdog timer and programmable startup signalvalues for each bit.The communications watchdog timer can be usedto move the digital output signals to a known “safe”condition in the event of a communications failure.

    COMMUNICATIONS
    The D6000 series modules are designed toeasily interface with computers and PLC’s. Allcommunications to and from the module areperformed using the Modbus RTU protocol via anRS485 interface.The two-wire RS485 system is a half duplex system,developed for multi-dropped systems that cancommunicate at high data rates over long distances.RS485 receivers can handle common mode voltagesfrom -7 to 12V without loss of data, making them idealfor transmission over great distances.

    MODBUS® COMMAND SET
    The D6000 series modules use the Modbus RTUprotocol for communications. The Modbus RTUbinary protocol uses a master-slave technique, inwhich only themasterdevice can initiate transactions.The slave devices respond by supplying the requesteddata to themasteror by performing the requestedaction in the query. Themastercan address anyslave device. The returned messages are consideredresponse messages. The supportedmasterfunctioncodes are:
    Modbus RTU Functions and Descriptions
    01 – Read Coil Status
    02 – Read Register Status
    03 – Read Holding Registers
    04 – Read Input Register (Analog Inputs)
    05 – Force Single Coil
    06 – Preset Single Register
    0F – Force Multiple Coils
    10 – Preset Multiple Registers

    PROCESS CONTROL SOFTWARE
    Modbus RTU protocol is one of the most widelysupported serial protocols in the data acquisitionmarket. Modbus RTU software drivers are availablefor almost every data acquisition software programavailable today. Thus providing instant connectivitybetween the D6000 modules and most dataacquisition software programs.

    SETUP
    The D6000 series are initiated at the factory usingthe Modbus RTU protocol. Features such as theModbus device address, baud rate, and analogsignal ranges can be easily configured using thesetup software. Each D6000 module must be properlyconfigured before installation into a Modbus system.

    UTILITY SOFTWARE
    Complimentary Utility Software is included with eachpurchase order. The software is compatible withWindows® operating systems and distributed onCD-ROM. The Utility Software simplifies configurationof all user selectable options such as device address,baud rate and filtering constants. The latest versionof our software is always available on our web site atomega.com.

    SPECIFICATIONS
    D6000
    (Typical @ 25°C and nominal power supplyunless otherwise noted)
    GENERAL
    Programmable Digital Filters:
    In analog input modules
    Maximum CMV (Input to Output at 115Vrms, 60Hz):500V rms
    Setups: Stored in EEPROM
    Unused Analog Input Channels: Software disable

    INTERFACE
    Communications: Modbus RTU protocol/RS485 Serial port

    SERIAL COMMUNICATIONS
    Baud Rates: 9600, 19.2K, 38.4K, 57.6K, 115.2K
    Data Format: 8 data bits, and 1 or 2 stop bits
    Parity: Odd, even, none
    Channel Address: User selectable
    Number of Modules: Up to 247 multi-drop modules perhost serial port
    Communications Distance: Up to 1219 m (4000') (RS485)
    Transient Suppression: On RS485 data lines

    POWER REQUIREMENTS
    Unregulated 10V to 30 Vdc, protected against powersupply reversals

    ENVIRONMENTAL
    Operating Temperature Range:-25 to 70°C (-13 to 158°F)
    Storage: -25 to 85°C (-13 to 185°F)
    Relative Humidity: 0 to 95% non-condensing

    PACKAGE, DIMENSIONS AND CONNECTORS
    Case: ABS thermoplastic, UL-94-5VA rated
    Dimensions:102 H x 152 W x 38 mm D (4 x 6 x 1.5");
    mounting holes165 mm (6.6") on center
    Connectors: Screw terminal barrier plug (supplied)

    MODULE SPECIFICATIONS
    D6100 Voltage Inputs
    Number of Channels: 7 differential voltage inputs
    Ranges: ±0.025V, ±0.05V, ±0.1V, ±1V, ±5V, ±10V
    Resolution ADC: 16-bit ADC, 25/20 conversions per second
    Accuracy: ±0.05% of FS maximum
    Span Tempco: ±50ppm/°C maximum
    Input Burnout Protection: To 250 Vac
    Input impedance: 20 MΩ min
    Power Requirements: Serial = 1.4W

    D6200 CURRENT INPUTS
    Number of Channels: 7 differential current inputs
    Range: ±20 mA
    Resolution ADC: 16-bit ADC, 25/20 conversions per second
    Accuracy: ±0.05% of FS maximum
    Span Tempco: ±50ppm/°C maximum
    Voltage Drop: 2.0V maximum
    Input impedance: <100 Ω (70 typical)
    Power Requirements: Serial = 1.4W

    D6300 THERMOCOUPLE IPUTS
    Number of Channels: 7 differential thermocouple inputs
    Thermocouple Types: J, K, T, E, R, S, B, and C
    Ranges:
    J = -200 to 760°C (-328 to 1400ºF)
    K = -150 to 1250°C (-238 to 2282ºF)
    T = -200 to 400°C (-328 to 752ºF)
    E = -100 to 1000°C (-148 to 1832ºF)
    R = 0 to 1750°C (32 to 3182ºF)
    S = 0 to 1750°C (32 to 3182ºF)
    B = 0 to 1820°C (32 to 3308ºF)
    C = 0 to 2315°C (32 to 4199ºF)
    Thermocouple Accuracy
    (Error From all Sources) from 0 to 40°C Ambient:

    J, K, T, E = ±1.5°C maximum;R, S, B, C = ±3.5°C maximum; (300°C to +F.S.)
    Resolution ADC: 16-bit ADC, 25/20 conversions per second
    Input Impedance: 20 MΩ min
    Cold Junction Compensation: Automatic
    Lead Resistance Effect: <40 µV per 350 Ω
    Indication: Open thermocouple and over range indication
    Input Burnout Protection: To 250 Vac
    Power Requirements: Serial = 1.4W

    D6400 VOLTAGE, THERMOCOUPLE, CURRENT INPUTS
    Number of Channels: 7 differential voltage,thermocouple, current inputs
    Specifications: Equal to D6100, D6200 and D6300 series

    D6500 ANALOG OUTPUTS
    Number of Channels: Two analog outputs(programmable for voltage or currrent output)
    Voltage Range: 0 to 10 Vdc, ±10 Vdc
    Current Ranges: 0 to 20 mA, 4 to 20 mA
    Update Rate: 250 conversions per second
    Accuracy: ±0.1%
    DAC Resolution: 12-bit
    Span Tempco: ±25ppm/°C maximum
    Settling Time to 0.1% FS: 1 mS
    Communications: Watchdog timer
    Current Output Compliance: ±12 Vdc
    Voltage Output Drive: 5 mA maximum
    ADC Analog Output Signal Readback: 8-bit
    Isolation: 500 Vac, output common to system ground
    Current Output Burnout: Protected to 250 Vac
    Power Requirements: Serial = 2.1W

    D6710 DIGITAL INPUTS
    Number of Channels: 15 digital inputs
    Internal: 10K pull-up resistors on each bit acceptdirect switch closure
    Logic “0”: <1Vdc, Logic “1”: = >3.5Vdc
    Input Burnout: To ±30 Vdc without damage
    Isolation: 500 Vac, input common to system ground
    Power Requirements: Serial = 0.75W

    D6720 DIGITAL OUTPUTS
    Number of Channels: 15 Open-collector outputs to30 Vdc, 100 mA maximum
    Vsat: +0.3 Vdc maximum at 100 mA
    Short Circuit Protection: To 500 mA
    Communications: Watchdog timer
    Digital Output Update Rate: 4.5 Hz
    Isolation: 500 Vac, output common to system ground
    Power Requirements: Serial = 1.0W

























































暂无内容提供
暂无内容提供

联系方式

中国自动化网安全提示,在购买供应商商品时,请一定要先审核好企业信息是否真实,谨防网上诈骗。
公司名称:Omega工业测量(中国)
联系人: 王先生
联系电话:02161973664
手机号:
传 真:
电子信箱:kevin.wang@cn.omega.com
公司网站:http://cn.omega.com
公司地址:上海市宜山路1698号102单元
留言反馈
  • 评价:

  • 关于:

  • 联系人:

  • 联系电话:

  • 联系邮箱:

  • 需求意向:

  • 验证码:

    看不清楚?

  • 在线咨询
X
下载企业APP

成为企业会员免费生成APP!